Rectification Measures And Restoration Of Distressed Pump Foundations

Deep Foundations Institute
Sampat Raj V K. Panwar
Organization:
Deep Foundations Institute
Pages:
8
File Size:
1373 KB
Publication Date:
Nov 1, 2022

Abstract

At a Fertilizer plant located in the southern part of India, 74 numbers of pump foundations have shown non-uniform settlements causing the tilting of pump foundations under self-weight primarily due to the presence of varying thickness of the heterogeneous subsoil beneath the pump foundations and soil erosion because of water seepage through deeper excavations in the close vicinity. Various corrective measures have been explored and taking due cognizance of the prevailing subsoil conditions, site constraints, and constructability aspects, micropiling has been adopted. This paper presents the site problem and details of remedial measures adopted for rehabilitation of the distressed pump foundations. The main objective of this paper is to provide guidelines for designer during design and detail engineering stage to avoid similar nature of problems and also to provide a solution concept to tackle similar nature of problem(s) if encountered at site.
Citation

APA: Sampat Raj V K. Panwar  (2022)  Rectification Measures And Restoration Of Distressed Pump Foundations

MLA: Sampat Raj V K. Panwar Rectification Measures And Restoration Of Distressed Pump Foundations. Deep Foundations Institute, 2022.