Discriminating Protection For Trolley Wires

The National Institute for Occupational Safety and Health (NIOSH)
D. A. Paice A. B. Shimp
Organization:
The National Institute for Occupational Safety and Health (NIOSH)
Pages:
11
File Size:
450 KB
Publication Date:
Jan 1, 1975

Abstract

Illegitimate loads on a mine dc power distribution system can be detected by measuring a superimposed ac current. To implement such a scheme, a 10-volt, 3-kHz voltage is applied at each dc power substation. By this means, the mine dc power distribution network, consisting of a feeder and trolley wires with a grounded rail return, is caused to serve also as a 3-kHz ac distribution network.